We Produce a wide range of Cables required in different categories. Some of our Products are as follows .
>> Computer Networking Cable / LAN Cable / CAT 5
>> Telephone Cables
>> Power Cables
>> Control Cables
>> Flexible Cables to IS:694
>> CCTV Cables   
Technical Specification Accepted >>GO
Products
Technical Accepted
Test Certificate -

We provide test certificate detailing test results obtained in our factory with every drum that we dispatch.

Bending Radius -

While installation of PVC insulated heavy duty cables of 650/1100 volts grade, bending radius should no be less than the following -

I. Single Core Cables - 15 times the overall diameter of Cables.

II.Multi Core Cables - 12 times the overall diameter of Cables.

Current Ratings

The continous current ratings and the rating factors for PVC insulated Heavy Duty Cables, given here are generally in accordance with IS: 3961(Pt.II)1967.

Basic Assumptions

The current ratings are based on the following installation conditions -

I. Maximum conductor temparature 70° C.

II. Thermal resistivity of soil 150° C cm/w.

III. Thermal resistivity of PVC 650° C cm/w.

IV. Ground Temparature 30° C.

V. Ambient air temparature 40° C.

VI. Depth of laying (to the highest point) of cable laid direct in the ground 75 cm.

Short Circuit Current Rating of Aluminium for 1 Second Duration.



Short Circuit Ratings of Starcab Cables can be calculated by using the following formula 
       lsh = KA / sqrt ( t ) 
where 
   lsh - Short circuit current im amps.
   A - Conductor area in sq. mm.
   t - duration of short circuit in second.
   K - 75.80 for Aluminium Cables.
   K - 109.00 for Copper Cables.

Nominal area of conductor in sq.mm.
Short Circuit Current in Kilo Amps.
Aluminium
Copper
1.50
0.11
0.16
2.50
0.19
0.27
4.00
0.30
0.43
6.00
0.45
0.65
10.00
0.76
1.00
16.00
1.20
1.70
25.00
1.90
2.72
35.00
2.63
3.81
50.00
3.56
5.45
70.00
5.14
7.63
95.00
7.14
10.35
120.00
9.01
13.00
150.00
11.10
16.35
185.00
13.90
20.16
240.00
18.50
26.16
300.00
22.90
32.70
400.00
29.30
43.60
500.00
36.90
54.50
Rating factors for Multi-core control cables with number of cores 5 and above.
No of loaded Cores
5
6
7
10
12
14
16
19
24
27
30
37
44
48
52
56
61
Rating factor
0.72
0.67
0.63
0.55
0.52
0.49
0.47
0.44
0.40
0.38
0.37
0.34
0.32
0.30
0.29
0.28
0.27
Rating Factors for variation in ambient air/ground temparature.
Ambient air/ground temparature °C
15
20
25
30
35
40
45
Air
-
-
1.25
1.16
1.09
1.00
0.90
Ground
1.17
1.12
1.06
1.00
0.94
0.87
0.79
Website Designed & Hosted by EasyTech